District Cooling networks Base Substastions
Gasketed and brazed plate heat exchangers.
50 to 1.000 kW standard package.
With heat meter, control and security devices.
PN 25 on primary circuit.
Twin heat exchangers version (max 5.000 kW). User customizable. CE / PED Certification.
Small size. Easy to disassemble and move.
Ready for remote metering and remote control.
Flow rate, power and return temperature limitation.
Temperature management for fixed-point or external temperature compensated.
HOT WATER | SUPERHEATED WATER | COOLING | DIRECT H.D.W. (Hot Domestic Water) | INDIRECT H.D.W. (Hot Domestic Water) | |
---|---|---|---|---|---|
THERMAL DESIGNPRIMARY CIRCUIT | 90/65°C | 115/65°C | 7/11°C | 85/55°C | 85/55°C |
THERMAL DESIGNSECONDARY CIRCUIT | 60/75°C | 60/75°C | 14/8°C | 25/50°C | 30/55°C |
PRESSURE LOSS (Δp) @ NOMINAL CONDITIONS - CIRCUITS 1 & 2 | < 10 w.c.m. (1°)< 3 w.c.m. (2°) | < 10 w.c.m. (1°)< 3 w.c.m. (2°) | < 15 w.c.m. (1°)< 6 w.c.m. (2°) | < 10 w.c.m. (1°)< 3 w.c.m. (2°) | < 10 w.c.m. (1°)< 3 w.c.m.(2°) |
MECHANICAL DESIGNCIRCUITS 1 & 2 | PN25PN16 | PN16PN10 | PN25PN10 | ||
THERMAL OVERSIZING | 20% | ||||
CERTIFICATION DESIGN | CE/PED - ISPESL | ||||
ΔP EMERGENCY CLOSEDOWNREGULATION VALVE | 25 barg | ||||
OPTIMIZATIONS | FLOW RATE LIMITATION, REMOTE SIMULTANEOUS TEMPERATURE AND POWER SETTING |
Type | Model | DN 1° (in/out) |
DN 2° (in/out) |
PN 1° (bar) |
PN 2° (bar) |
Tmax 1° (°C) |
Tmax 2° (°C) |
Dimensions (mm) |
Weight (kg) |
---|---|---|---|---|---|---|---|---|---|
Cold Water Cooling Gasketed | BIELLA 1000 F | 200/200 | 200/200 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x950x2100 | 1350 |
Cold Water Cooling Gasketed | BIELLA 100 F | 50/50 | 80/80 | 16.0 | 10.0 | 95.0 | 95.0 | 1800x870x1650 | 300 |
Cold Water Cooling Gasketed | BIELLA 1250 F | 200/200 | 200/200 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x1900x2100 | 2300 |
Cold Water Cooling Gasketed | BIELLA 1500 F | 250/250 | 250/250 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x1900x2100 | 2550 |
Cold Water Cooling Gasketed | BIELLA 150 F | 65/65 | 80/80 | 16.0 | 10.0 | 95.0 | 95.0 | 1800x870x1650 | 350 |
Cold Water Cooling Gasketed | BIELLA 2000 F | 250/250 | 250/250 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x1900x2100 | 2700 |
Cold Water Cooling Gasketed | BIELLA 200 F | 80/80 | 80/80 | 16.0 | 10.0 | 95.0 | 95.0 | 1800x870x1650 | 350 |
Cold Water Cooling Gasketed | BIELLA 2500 F | 300/300 | 300/300 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x1900x2100 | 3200 |
Cold Water Cooling Gasketed | BIELLA 250 F | 100/100 | 100/100 | 16.0 | 10.0 | 95.0 | 95.0 | 1800x870x1650 | 400 |
Cold Water Cooling Gasketed | BIELLA 300 F | 100/100 | 100/100 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x950x2100 | 850 |
Cold Water Cooling Gasketed | BIELLA 350 F | 100/100 | 100/100 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x950x2100 | 950 |
Cold Water Cooling Gasketed | BIELLA 400 F | 125/125 | 125/125 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x950x2100 | 950 |
Cold Water Cooling Gasketed | BIELLA 500 F | 125/125 | 125/125 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x950x2100 | 1100 |
Cold Water Cooling Gasketed | BIELLA 50 F | 50/50 | 80/80 | 16.0 | 10.0 | 95.0 | 95.0 | 1800x870x1650 | 250 |
Cold Water Cooling Gasketed | BIELLA 600 F | 150/150 | 150/150 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x950x2100 | 1150 |
Cold Water Cooling Gasketed | BIELLA 700 F | 150/150 | 150/150 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x950x2100 | 1250 |
Cold Water Cooling Gasketed | BIELLA 75 F | 50/50 | 80/80 | 16.0 | 10.0 | 95.0 | 95.0 | 1800x870x1650 | 300 |
Cold Water Cooling Gasketed | BIELLA 800 F | 150/150 | 150/150 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x950x2100 | 1250 |
Cold Water Cooling Gasketed | BIELLA 900 F | 200/200 | 200/200 | 16.0 | 10.0 | 95.0 | 95.0 | 3050x950x2100 | 1350 |