HIU ultra compact single dwelling unit substations

10÷60 kW heating and up to 80 kW Hot Domestic Water production.

mono_2_0

standards

ACQUA_CALDA ACQUA_SURRISCALDATA ACS ACS_DIRETTA SOLO_RISC
From 10 to 80 kW
Model "Bolzano"

From 10 to 60 kW standard construction for heating and up to 80 kW for domestic hot water (DHW). Available in heating or DHW versions.
Equipped with a heat meter, controls, and safety devices.
PN 25 primary circuit.
For networks with hot water or overheated water.
For heating and/or domestic hot water use. Customization according to customer needs.
CE/PED certification and approval.
Very compact dimensions.
Easy maintenance.
Prepared for remote reading and remote control.
Setting for flow rate limitation, power, and return temperature.
Management of fixed-point temperature or temperature compensation with outside temperature.

Strength

RANGE AND PERFORMANCES

  • 12 models for heating and DHW use for networks with hot water and overheated water.
  • Base version wall-mounted, wall-mounted version, design version.
  • Heating thermal power from 18 to 40 kW.
  • Instantaneous DHW production from 13 to 22 liters/minute

MANAGEMENT

  • Setting and regulation of heating water and DHW temperature via configurable PID controller.
  • Operator panel with remote-controllable chronothermostat function up to 30 meters away with integrated ambient temperature sensor.
  • Prepared for remote reading and remote control via unified standard Meter-bus protocol or other unified protocol.
  • Dedicated software for easy-to-use individual metering and remote control. Integration with existing or superior remote control systems.
  • 6 implemented limits: limits for secondary flow and primary return temperature, flow limit, and power limit for both heating and DHW functions.

SPECIAL FUNCTIONS AND SERVICES

  • Legionella prevention function.
  • Anti-scale function

CONSTRUCTION

  • Extremely compact dimensions (500 mm width x 800 mm height x 160 mm depth).
  • Powder-coated carbon steel frame.
  • Robust mechanical construction without the use of hydraulic groups in plastic materials.
  • Primary circuit design temperature: 135°C
  • Primary circuit design pressure: PN25
  • Secondary circuit and DHW design pressure: PN10
  • Nominal thermal conditions for primary circuit: 90/65°C
  • Nominal thermal conditions for secondary circuit: 80/60°C
  • CE/PED approval for all models obtained with Ispesl certification body, with safety redundancy beyond what is required by regulations.
  • Non-return valve on the primary circuit.
  • Manual reset lockout thermostat.
  • Automatic reset control thermostat.
  • Expansion vessel.
  • Stainless steel mesh filter on the primary, secondary, and DHW circuits.
  • Ultrasound static heat meter approved EN 1434/MID.
  • Main suppliers of components used by Amarc DHS on its products: ALFA LAVAL (heat exchangers) | DANFOSS (control valves, actuators, regulators) SIEMENS (heat meters, control valves, actuators, regulators) | KAMSTRUP (heat meters) | BRANDONI (intercept valves, non-return valves) | NAVAL OY (ball valves) | IVR (intercept valves) | CALEFFI/WATTS (safety valves) | WILO (pumps) | HONEYWELL (actuators, two-way and three-way control valves).

Common schematic

Working Conditions

HOT WATER SUPERHEATED WATER DIRECT H.D.W. INDIRECT H.D.W.
THERMAL DESIGNPRIMARY CIRCUIT 90/65°C 115/65°C 85/55°C 85/55°C
THERMAL DESIGNSECONDARY CIRCUIT 60/75°C 60/75°C 25/50°C 30/55°C
PRESSURE DROP (Δp) @ NOMINAL CONDITIONS - CIRCUITS 1 & 2 < 10 w.c.m. (1°)< 3 w.c.m. (2°) < 10 w.c.m. (1°)< 3 w.c.m. (2°) < 10 w.c.m. (1°)< 3 w.c.m.. (2°) < 10 w.c.m. (1°)< 3 w.c.m. (2°)
MECHANICAL DESIGNCIRCUITS 1 & 2 PN25 (1°)PN16/PN10 (2°) PN25 (1°)PN10 (2°)
THERMAL OVERSIZING 20%
CERTIFICATION DESIGN CE/PED - ISPESL
ΔP EMERGENCY CLOSEDOWNREGULATION VALVE 25 barg
OPTIMIZATIONS FLOW RATE LIMITATION, REMOTE SIMULTANEOUS TEMPERATURE AND POWER SETTING

Our models

Type Model DN 1°
(in/out)
DN 2°
(in/out)
PN 1°
(bar)
PN 2°
(bar)
Tmax 1°
(°C)
Tmax 2°
(°C)
Dimensions
(mm)
Weight
(kg)
Hot Water Heating Brazed plate BOLZANO 10 C ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 30
Overheated Water Heating Brazed plate BOLZANO 10 S ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 30
Hot Water Heating Brazed plate BOLZANO 15 C ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 30
Overheated Water Heating Brazed plate BOLZANO 15 S ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 30
Hot Water DHW-Direct Brazed plate BOLZANO 20 C ACS D ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Hot Water DHW-Indirect Brazed plate BOLZANO 20 C ACS I ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Hot Water Heating Brazed plate BOLZANO 20 C ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 30
Overheated Water DHW-Direct Brazed plate BOLZANO 20 S ACS D ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Overheated Water DHW-Indirect Brazed plate BOLZANO 20 S ACS I ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Overheated Water Heating Brazed plate BOLZANO 20 S ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 30
Hot Water Heating Brazed plate BOLZANO 25 C ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 30
Overheated Water Heating Brazed plate BOLZANO 25 S ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 30
Hot Water DHW-Direct Brazed plate BOLZANO 30 C ACS D ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Hot Water DHW-Indirect Brazed plate BOLZANO 30 C ACS I ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Overheated Water DHW-Direct Brazed plate BOLZANO 30 S ACS D ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Overheated Water DHW-Indirect Brazed plate BOLZANO 30 S ACS I ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Hot Water Heating Brazed plate BOLZANO 35 C ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 30
Overheated Water Heating Brazed plate BOLZANO 35 S ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 30
Hot Water DHW-Direct Brazed plate BOLZANO 40 C ACS D ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Hot Water DHW-Indirect Brazed plate BOLZANO 40 C ACS I ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Overheated Water DHW-Direct Brazed plate BOLZANO 40 S ACS D ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Overheated Water DHW-Indirect Brazed plate BOLZANO 40 S ACS I ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Hot Water Heating Brazed plate BOLZANO 45 C ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 30
Overheated Water Heating Brazed plate BOLZANO 45 S ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 30
Hot Water DHW-Direct Brazed plate BOLZANO 50 C ACS D ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Hot Water DHW-Indirect Brazed plate BOLZANO 50 C ACS I ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Overheated Water DHW-Direct Brazed plate BOLZANO 50 S ACS D ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Overheated Water DHW-Indirect Brazed plate BOLZANO 50 S ACS I ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Hot Water DHW-Direct Brazed plate BOLZANO 60 C ACS D ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Hot Water DHW-Indirect Brazed plate BOLZANO 60 C ACS I ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Overheated Water DHW-Direct Brazed plate BOLZANO 60 S ACS D ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Overheated Water DHW-Indirect Brazed plate BOLZANO 60 S ACS I ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Overheated Water Heating Brazed plate BOLZANO 60 S ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 30
Hot Water DHW-Direct Brazed plate BOLZANO 70 C ACS D ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Hot Water DHW-Indirect Brazed plate BOLZANO 70 C ACS I ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Overheated Water DHW-Direct Brazed plate BOLZANO 70 S ACS D ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Overheated Water DHW-Indirect Brazed plate BOLZANO 70 S ACS I ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Hot Water DHW-Direct Brazed plate BOLZANO 80 C ACS D ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Hot Water DHW-Indirect Brazed plate BOLZANO 80 C ACS I ¾” 1” 25.0 10.0 110.0 95.0 500x600x150 28
Overheated Water DHW-Direct Brazed plate BOLZANO 80 S ACS D ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28
Overheated Water DHW-Indirect Brazed plate BOLZANO 80 S ACS I ¾” 1” 25.0 10.0 130.0 95.0 500x600x150 28